Determining Concrete Setting Times Using ASTM C403M-16 Standards

In construction and project sites, as well as in laboratory settings, the penetration resistance test plays a crucial role in assessing the initial and final setting times of concrete mixtures. Various factors, such as water content, the type and amount of cementitious material, and admixtures, can influence the concrete’s setting time. This test involves analyzing a sieved mortar sample to understand the hardening process.

Understanding Setting Times: Initial and Final

The initial setting time marks the point at which cement begins to harden, losing its plasticity. On the other hand, the final setting time signifies when the concrete loses its plasticity entirely and solidifies. As per ASTM C403M-16 standards, these times are determined when the penetration resistance reaches specific values, namely 3.5 MPa for initial setting and 27.6 MPa for final setting.

Factors Influencing Setting Times

Several factors can impact the setting times of concrete. The fineness of cement, the presence of salts in sand, and atmospheric conditions all play a role. For instance, cement requires a temperature of 27°C for complete hydration, but in colder weather, the hydration process takes longer.

Apparatus Used in the Test

  1. Container:
    • Lateral dimension: At least 150 mm
    • Height: At least 150 mm
  2. Penetration Needles:
    • Various sizes with specific bearing areas
  3. Loading Apparatus:
    • Measures force required for penetration
    • Accuracy: 10 N, Capacity: At least 600 N
  4. Tamping Rod:
    • Round and straight, 16 mm diameter, 600 mm length
  5. Pipet:
    • Used for drawing off bleed water
  6. Thermometer:
    • Measures temperature up to 60.5°C
  7. Stop Watch

Sample Preparations

  • Representative samples obtained for field and laboratory tests.
  • Concrete passed through a 4.75-mm sieve used for specimen preparation.
  • For compliance testing, at least three separate batches prepared for each variable.
  • Initial contact time recorded, mortar mixed thoroughly, and temperature measured.
  • Specimen prepared in a container, removing air pockets, and leveling the top surface.

Procedures of Concrete Setting Time Test

  1. Eliminate bleed water using a pipet.
  2. Choose needle size based on mortar setting time.
  3. Bring needle into contact with mortar surface.
  4. Apply vertical force until the needle penetrates to 25±2 mm.
  5. Record force and time of load application.
  6. Calculate penetration resistance by dividing force by needle’s bearing area.

Precautions For Subsequent Tests

  • Maintain a minimum distance of 15 mm between needle impressions.
  • Clear distance between any impression and container side: 25-50 mm.
  • For conventional concrete at 20-25°C, initial test after 3-4 h, subsequent tests at 1?2-1 h intervals.
  • Concrete with accelerators: Initial test after 1-2 h, subsequent tests at 1?2-h intervals.
  • Concrete with retarders: Initial test after 4-6 h.
  • Make at least six penetrations for each time-of-setting test.

Graphing Test Results

  • Plot penetration resistance vs. elapsed time.
  • Use a scale representing 3.5 MPa and 1 h by at least 15 mm.
  • Visually identify initial and final setting times.

Sources of Errors

  • Larger particles in mortar.
  • Presence of voids within the penetration zone.
  • Interference from adjacent penetrations.
  • Failure to maintain instrument perpendicular.
  • Errors in reading load variations.

In conclusion, the penetration resistance test, conducted in accordance with ASTM C403M-16, provides valuable insights into the setting times of concrete mixtures, aiding in effective construction and project management. Understanding the apparatus, procedures, precautions, and potential errors ensures accurate and reliable results.

Leave a comment